Contact us   ask a question

AC-M7MKII

Tent cooling

The AC-M7MKII air conditioner is a 7-kW portable unit developed primarily to provide air conditioning in temporary or transportable buildings or tents. The AC-M7MKII is designed to be placed outside the tent with ducted supply and return air.

  • Features

    • Manufactured from hot dip galvanized and powder coated steel sheet
    • Can provide cooling at ambient temperatures up to +55°C
    • Connect to the mains power supply or a separate diesel generator through a 15m power cable with CEE plug
    • “VENT-only” option, allowing ventilation without cooling
    • Temperature control by a room thermostat placed inside the tent
    • Washable and easy removable coarse filters in front of internal air intake as well as in front of external air intake
    • Easy transportation, either by forklift, the four lifting hooks on top of the unit or with the two wheels
    • Setup and operation can be done by a single person
    • Removable wheels, which can be stowed on top of the unit

    Optional accessories

    • Remote thermostat with cable, 15m
    • Insulated, flexible air duct Ø315 x 3000mm incl. bag
    • Non insulated, flexible air duct Ø315 x 5000mm
    • Non insulated, flexible air distribution duct Ø315 x 5000mm
    • Non insulated, flexible air distribution extension duct Ø315 x 2000mm
    • Insulated, flexible air duct Ø225x3000mm
    • Storage bag for insulated air duct Ø225
    • Non insulated, flexible air distribution duct Ø225 x 6000mm

    Applications

    • Tents
    • Field hospitals
    • Military camps
    • Relief camps
    • Temporary buildings
  • Mobile Brochure

    Dantherm Group

    Mobile Brochure

    Mobile Heating and Cooling Catalogue

    Dantherm Group

    Mobile Heating and Cooling Catalogue

  • Specifications Units AC-M7MKII
    Operating temperature range, cooling °C 20-55
    Operating temperature range, heating °C -20 - +20
    Air flow m³/h 2500
    Sound level @ 1m dB(A) 69
    Refrigerant R134a
    Max. cooling capacity kW 7.6
    Heating capacity (with electric heating element) kW 7.2
    Power supply (60 Hz available) V/Hz 400/3ph/50
    Max. running current, cooling/heating A 7.2/13
    Locked rotor amperage (LRA), cooling A 24
    Max. power consumption cooling/heating W 3700/7700
    Hose connection Ø mm 1 x 315 or 2 x 225
    Product size (h x l x w) mm 1150 x 796 x 756
    Weight kg 190
  • Please click on images to view larger

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

    AC-M7MKII in situ

Gert Jensen

Military Heating & Cooling
Direct: +45 96 14 37 38
Mobile: +45 22 18 32 25

Contact Gert

  • Facebook
  • Twitter
  • linkedin
  • youtube